Products
MV-WM0006 Beam-Type Weigh Module for Vessel Supports
video
MV-WM0006 Beam-Type Weigh Module for Vessel Supports

MV-WM0006 Beam-Type Weigh Module for Vessel Supports

Brand: METRAVON

Model: MV-WM0006

Output: Load-cell signal and any transmitter output to be specified separately

Power Supply: Confirm fitted load-cell excitation and instrument bridge-drive capacity

Ingress Protection: Obtain the supplied sensor and assembly material and ingress specification

Measuring Range: 0.5-2.5 t and 3-5 t reference groups; rating applies per module

Description: Select METRAVON MV-WM0006 beam-type weigh modules for vessel supports. Compare capacity groups, mounting pitches and installed height, then request a configured quote.

Product Details

METRAVON MV-WM0006 is a beam-type weigh module with upper and lower mounting plates and a threaded load-transfer assembly. The reference drawing covers 0.5-2.5 t and 3-5 t capacity groups. Both use a 127 mm upper plate and 101.6 mm fixing pitch, but their base lengths and installed heights differ. Select it from the highest reaction at each vessel support and the complete rated outline, not from the old support height alone.

METRAVON MV-WM0006 beam-type weigh module with upper plate, threaded load transfer and lower base
MV-WM0006 beam-type weigh module. Match both mounting plates and the rated assembly height before replacing a vessel support.

Calculate the service load before selecting a capacity

Add the empty vessel, maximum contents, agitator, insulation, platforms and any permanently attached equipment. Divide by the number of supports, then assess unequal distribution, filling impact, agitation, wind or seismic action and maintenance loads. One support can carry more than the average when the center of gravity is offset or the foundation levels differ.

The module rating applies at each support. Do not use the combined nominal capacity as the only selection rule, and do not assume every support receives an equal share. The vessel structure and foundation must be stiff enough to deliver load consistently to all modules.

Match the beam-type weigh module to both mounting plates

The two capacity groups share the upper plate dimensions but use different base fixing pitches, plate thicknesses and height references. A common top plate does not establish a drop-in replacement. Measure the existing foundation and vessel bracket separately, including bolt access and the clearance needed to unload or remove the sensor.

Drawing referenceValueInstallation check
0.5-2.5 t: H / L100-120 / 180.9 mmHeight reference and overall base length.
3-5 t: H / L130-150 / 215.9 mmThe higher-capacity base is longer and taller.
0.5-2.5 t: J152.4 mmBase fixing pitch; compare with the foundation.
3-5 t: J177.8 mmDifferent from the lower-capacity base pitch.
Both groups: A / B127 / 101.6 mmUpper plate size and fixing pitch.
Both groups: F / G / D127 / 101.6 / 16 mmBase width, transverse pitch and hole diameter.
0.5-2.5 t: C / E18 / 18 mmUpper and lower plate thicknesses.
3-5 t: C / E26 / 26 mmCheck bolt grip and support clearance.

H is the assembly-height interval shown in the outline; it is not a permitted travel, uplift rating or adjustment instruction. Obtain the approved setting and restraint clearances for the offered assembly. A taller replacement can preload rigid pipework as the vessel is lowered, so plan temporary support and check the empty-vessel reading after every connection is restored.

Define what the dynamic-load duty actually requires

The reference identifies this as a dynamic-load module, but its outline does not give a weighing speed, vibration tolerance, settling time or certified in-motion performance. Describe agitator operation, filling impact and the state in which a weight is accepted. If batching depends on a stable reading while material is moving, test that operating sequence with the selected sensor and instrument. The module name alone does not establish the control response.

Pipes and restraints can bypass the weighing system

A rigid inlet, outlet or service pipe can pull on the vessel as product temperature changes. The resulting vertical or horizontal force appears as zero shift, poor return to zero or a weight change unrelated to product. Use flexible connections where the process permits, support external pipes independently and arrange them symmetrically when possible.

Ladders, platforms, grounding straps and safety restraints can create the same problem. They must protect the vessel without becoming an uncontrolled parallel load path. For outdoor vessels, the restraint design must also address uplift and overturning; the weigh module should not be treated as the only structural safety device.

Installation sequence for a multi-support vessel

  1. Survey the foundation elevations and correct soft, twisted or uneven support points.
  2. Position every module in the designed force direction and keep the upper and lower plates parallel.
  3. Use temporary supports or jacking points so welding current and erection loads do not pass through the sensors.
  4. Lower the vessel gradually, then check that every module is seated and able to move as intended.
  5. Connect pipes and accessories while monitoring zero so external preload is found before calibration.
  6. Set restraints and stops to their documented clearances after the vessel is in its operating position.

Specify the electrical scope separately

Order the module together with a defined sensor configuration: rated load, sensitivity, excitation, resistance, cable, material and protection rating. A mechanical module designation alone does not establish these electrical characteristics. For multiple supports, the instrument must have enough excitation capacity for all connected bridges.

State whether the scope includes only the modules, a junction box, a weighing indicator, a weight transmitter or a complete PLC interface. If 4-20 mA, RS485 or Modbus RTU is required, identify the instrument that provides it and define the displayed unit, scaling and communication settings.

Choose the weighing indicator after establishing whether the operator needs a local weight display, batch control or a signal for the PLC. The load-cell-to-PLC wiring guide explains where excitation, calibration and scaling belong in that signal path.

Calibrate the installed vessel

Bench data for an individual sensor cannot account for the completed structure, pipes and support balance. Calibrate after mechanical installation using traceable test weights, a substitution method or a documented material test appropriate to the vessel. Apply load in stages and record loading, unloading and return to zero.

Where individual support signals can be observed, compare them before combining the channels. A large imbalance may indicate an uneven foundation, restrained movement or an offset center of gravity. Do not trim a serious mechanical problem out of view at the junction box.

Diagnose weight changes before adjusting zero

Q1. Why does an empty tank change weight when a valve opens?

Pressure or pipe movement may be transmitting force into the tank. Record the indicated weight with the same empty vessel and repeat the valve operation under controlled conditions. Inspect pipe supports and flexible connections. Re-zeroing at one valve position can conceal a repeatable error that returns at the next operating state.

Q2. Why is one module's output much higher than the others?

Unequal weight distribution may be real, but also check foundation level, module seating and a restraint that is carrying load. Compare the outputs using each sensor's calibration data and actual excitation voltage. Equal millivolt readings are not a valid target when sensor capacities or sensitivities differ.

Q3. Can filtering make a mixing vessel suitable for precise batching?

Filtering can reduce display fluctuations, but it adds delay and does not remove the forces from agitation. Define when the batch is weighed, test the settling time and check whether the final cutoff overshoots with the selected filter. If the result is accepted only with mixing stopped, include that condition in the operating procedure.

Request the module and instrument together

Send the vessel support drawing for an MV-WM0006 quotation. Include empty and full weights, support positions, pipe connections, agitation, available installation height and the required weight signal. Identify outdoor exposure or corrosive cleaning conditions. Those details determine the capacity at each support, the mechanical arrangement and the electrical equipment needed to commission the vessel.

Send Form