Radar level commissioning is incomplete if the loop has only been checked while continuously powered. A transmitter may restart correctly while the PLC continues displaying an old value, or a receiver may initialise before valid sensor data is available. Test the installed restart sequence before relying on the loop during routine power interruptions.
Prepare a controlled restart test
Agree the plant state, authorised isolation point and required control response before interrupting power. Protect against unintended pump or valve action through the site's approved procedure. Do not test by casually pulling wires from a live process loop.
Record the accepted configuration, current physical level and receiver indication before the test. For the METRAVON MV-RD12, identify the actual electrical version: a two-wire 4-20 mA/HART loop and a separately powered RS485 arrangement do not have the same power path.

Radar level commissioning should cover the receiving system too
| Event | Evidence to capture |
|---|---|
| Sensor off | How the PLC marks unavailable measurement and what actions remain permitted. |
| Sensor on | Time until a valid current reading is available, with observed status and value. |
| Host restart | Whether the receiver restores the intended scale and waits for usable input. |
| Normal state | Removal of test overrides, correct alarms and the authorised return to automatic control. |
Use the actual observed startup interval and the supplied documentation. Do not insert a generic delay and call it a product specification. Where startup depends on the operating state or communication sequence, record the tested conditions and any additional cases required.
Confirm what survives the interruption
Read back the required settings after power returns: units, reference dimensions, assigned output and communication settings where applicable. Compare them with the accepted record. If values differ, investigate the save procedure and device documentation before repeating the test; do not assume every configuration tool writes persistent storage immediately.
Check fresh measurement separately from retained configuration. A PLC that restores the correct units can still show a cached level. Use available data-quality information and a safe reference observation to demonstrate that the signal is current. An unchanged liquid level alone cannot distinguish a new reading from an old one.
Document any automatic restart action. A restored numeric value should not silently release a process that requires operator acknowledgement or other checks. That release logic belongs to the approved control design, not to a presumed behaviour of the radar.
Restart questions
Q1. Is cycling the transmitter alone sufficient?
It tests one event. Assess separate receiver or communication-equipment restarts where they can affect the loop. The scope should reflect the installed architecture rather than an arbitrary list of devices.
Q2. Can we accept the loop as soon as a plausible number appears?
No. Confirm that the number is a valid new measurement, that its reference is correct and that test overrides are removed. Keep startup fault indications visible until the approved recovery conditions are satisfied.
Summary
Test loss, startup and recovery as a sequence. Provide the power arrangement and restart acceptance requirements when specifying MV-RD12 commissioning support, and retain the observed results with the final settings.
