Blog
Technical Articles

HART Level Integration: Decide Whether the Existing Analogue Loop Is Enough

2026-09-05

A plant that already uses 4-20 mA does not necessarily need a new digital bus to gain instrument information. HART level integration can retain the analogue process signal while adding supported digital communication. The useful question is whether the installed host can access the required functions, not whether the instrument name includes a protocol.

Start with the information the plant needs

Separate the continuous level used by the controller from occasional configuration access and maintenance diagnostics. A standard analogue input can read current without interpreting HART messages. A handheld connection may support local maintenance but does not establish that device information reaches the control room continuously.

HART combines analogue current with digital communication on a compatible loop. The supported variables and commands depend on the device and host. Confirm the exact MV-RD12 implementation and receiving hardware before promising remote echo access, additional process variables or asset-management functions.

Compare the integration paths

PathWhat must be confirmed
Analogue onlyThe level signal, receiver scale and required fault interpretation are sufficient for the duty.
Analogue with HARTLoop compatibility, host access and the particular digital functions needed by maintenance.
RS485 / Modbus RTUThe corresponding instrument version, power wiring, network design and documented register mapping.
Other fieldbusAn explicitly supported device or engineered interface; availability cannot be inferred from HART or RS485.
METRAVON MV-RD12 liquid radar with PTFE lens and flanged connection
Specify the MV-RD12 output version from the host requirements; HART and RS485 are not interchangeable interfaces.

The METRAVON MV-RD12 offers a two-wire 24 V DC 4-20 mA/HART route and a corresponding separately powered RS485 configuration. Select between those documented routes using the plant input and information requirements. Do not specify an unlisted fieldbus as though it were a standard option.

Check the whole loop for HART level integration

Review the input card, isolators, barriers and other series components for the required communication path. A component can pass the analogue current while not providing the intended digital access. Use the applicable electrical requirements and drawings rather than adding resistance from a generic rule without checking the voltage budget.

For an existing installation, identify where a maintenance tool can connect and whether that access is permitted during operation. Network or asset-management access also needs the site's security and change controls. Keep configuration permissions separate from routine observation where the host supports that distinction.

Q1. Does HART replace the PLC analogue scale?

Not when the controller still uses the current input for level. Verify that scale even if a maintenance tool independently displays a correct digital value.

Q2. Can an RS485 input read HART directly?

No. They are different interfaces. Any conversion requires a specifically supported device and a defined mapping; a wiring adapter alone is not sufficient.

Q3. When is keeping analogue-only integration reasonable?

Keeping the existing analogue input is reasonable when it meets the operating and maintenance requirements and its fault handling has been verified. Add digital access when it supplies information or functions that plant staff need and can use through the installed host.

Summary

Choose the interface from the information and access the plant will use. Provide the host card, loop drawing and required functions to compare the available MV-RD12 output configurations.

Related Product Categories

Browse product categories to quickly find a measurement solution suited to your application.

View All Products
Level MeasurementLevel SwitchesIndustrial WeighingWater Level & FlowData Acquisition

Get a Project Quote

Tell us the medium, measuring range, process conditions, mounting method, output signal and estimated quantity. We will recommend a suitable configuration and provide a quotation.